Slocable provides single-core aluminum conductor power cables, mainly medium-voltage underground cables. It is 26/35KV single-core aluminum conductor power cables, suitable for 50mm²-800mm², and is specially supplied for high-efficiency and reliable power applications.
|
Cable Material |
|
| Conductor | Compact round conductor |
| Conductor Shield | Semi-conductive screen compound (≤ 500 mm²); Semi-conductive tape + semi-conductive screen compound (≥ 500 mm²) |
| Insulation | Cross-linked polyethylene (XLPE) |
| Insulation screen | Strippable semi-conductive screen compound |
| Metallic screen | Copper tape; Copper wire screen (for 35 kV cables ≥ 500 mm²) |
| Filler | Non-hygroscopic filler rope (>1 Core) |
| Binder tape | Non-hygroscopic binding tape |
| Outer sheath | 90 °C PVC sheath |
|
Temperature Ratings |
|
| Maximum conductor operating temperature |
90 °C |
| Ambient operating temperature | –15 °C to +55 °C |
| Minimum installation temperature | ≥ 0 °C (Cable shall be preheated if ambient temperature is below 0 °C) |
Complete Model Range:
YJV/YJLV: Basic type, used indoors, in tunnels, and other applications without forced mechanical external force.
YJV22/YJLV22: Steel strip armored, used for direct burial, pipelines, and tunnels; cannot withstand tension or compression.
YJV23 / YJLV23: Steel strip armored, based on YJV22, with an outer sheath that is more resistant to moisture and chemical corrosion. Suitable for direct burial in humid and corrosive environments.
YJV62 / YJLV62: Non-magnetic stainless steel strip armored, prevents magnetic interference, suitable for AC systems, and prevents eddy current heating in the armor layer.
YJV72 / YJLV72: Steel wire armored, can withstand tensile and compressive stress. Suitable for vertical laying, underwater, or applications subject to tensile stress.
Excellent Insulation Performance
Slocable's medium-voltage cables have extremely high insulation resistance and dielectric strength, and can withstand the electric field stress of medium-voltage levels for extended periods without breakdown.
High safety level
Rigorous type and factory tests (such as partial discharge and AC withstand voltage tests) ensure 100% compliance with national standards.
Special flame-retardant and fire-resistant design allows for sustained power supply for a period under fire conditions, providing valuable time for critical equipment operation and personnel evacuation.